|
Introduction
The following guidance note is produced to give advice
on the suitability and use of automatic door release mechanisms. It aims
to set acceptable standards of safety and at the same time leaving scope
for flexibility and the exercise of judgment in relation to individual
circumstances. Before you make a decision on automatic door release mechanisms
have you considered swing free closers, these exert no forces on a door
leaf during normal operation. They may include internal sensors or be
linked to the fire alarm system. When activated by the sensor system,
or in the event of power failure, the closer system shuts the door in
the same way as a normal closer.
General Principles
The holding open of self-closing fire doors should
be discouraged in most cases however where they cause serious restriction
in the free movement of people within a building, you may need to consider
and install, where appropriate, automatic door release mechanisms.
A site-specific risk assessment should be carried out
and the following criteria should be appropriately applied: -
- The door release mechanism should conform to
an appropriate standard or be accredited as part of the European Construction
Product Directive.
- All doors fitted with automatic releases should be
actuated by an appropriate automatic fire detection and alarm system.
BS 5839 Parts 1 or 6 detail an acceptable standard.
- If devices are fitted to fire doors protecting the
means of escape then the automatic detectors should be positioned in
accordance with British Standard 5839 Part 1, for a Type L3 system as
minimum, for example suitable detectors on the means of escape routes
and in adjacent rooms opening onto those routes. If the means of escape
route is fire protected then either smoke or heat detectors are considered
suitable in the adjacent rooms, whilst if the route is unprotected,
only smoke detectors should be used.
- The practice of using dedicated smoke detectors either
side of corridor doors that are to be held open by a door release mechanism
should be discontinued. This is because studies have found that smoke
entering the corridor from an adjacent room may not have sufficient
buoyancy, movement and directional flow to actuate the dedicated detector
heads.
- All automatic door releases should be triggered
by each or any of the following: -
- The detection of smoke by automatic detection;
or
- The actuation of an alarm by a manual fire alarm
call point; or
- Failure of the fire warning system.
- Each automatic door release should be provided with
means of manual operation from a position at the door, closing door
by hand/foot is considered suitable.
- In sleeping risk premises each door fitted with an
automatic door release should be closed at a predetermined time each
night and remain closed throughout the sleeping hours. The method of
achieving this may be either automatic or manual, depending on the type
of release mechanism installed, but compliance with this will be a matter
for the management regime of the premises/workplace. Any remote or unsupervised
release of self-closing fire doors may injure occupants. The responsible
person should only carry out fire alarm tests and/or remotely release
self-closing fire doors if arrangements, so far as is reasonably practicable,
are in place to safeguard the occupants from injury. For instance an
occupant being struck by a door closing.
- The release mechanisms should be operated at
least once each week to ensure that: -
- The mechanisms are working effectively, and
- The doors are not warped and close effectively into
their frames
- The release mechanisms should operate within 20 seconds
of the fire alarm operating.
- Doors fitted with release mechanisms should be provided
with appropriate sign. Automatic Fire Door Keep Clear.
- The devices must be tested weekly, in association with
the testing of the fire alarm system, and maintained in accordance with
the manufacturer's instructions. A record should be kept of all testing
and maintenance activities. Doors fitted with such devices should be
kept closed during periods when the fire alarm system is isolated for
maintenance purposes.
Self-Contained Release Devices (SCRD)
SCRD are not normally directly connected to a fire alarm
system and it is important that additional points are taken into account
and/or considered when these types of devices are to be installed. These
points are set out below:
- Acceptance depends upon the outcome of a site-specific
risk assessment. They should not normally be used on doors protecting
single stairway buildings or protecting other critical means of escape.
- The fire alarm system should have a secondary power
supply to a standard as detailed in BS 5839: Parts 1 or 6.
- The fire alarm audibility level at the position of
any acoustically actuated device must be sufficient to ensure that the
mechanisms will release the door upon the actuation of the fire alarm
system.
- The management of the premises/workplace should
ensure that there are procedures in place, either manual or automatic,
to de-activate any or all of the devices in the following circumstances:
-
- When there is a fault in the fire warning system
- When the fire alarm system is isolated for any reason
e.g. Maintenance
- Any other circumstances when the sound of the fire
alarm will not trigger the device
- Self-contained devices should have their batteries
replaced at least every 12 months or when the low voltage-warning device
sounds.
The above information is from a guidance note issued
by Chief & Assistant Chief Fire Officers Association's NFSC on 20
March 2003
Costs
There was a time when cost of a fire safety solutions was
never considered and the fire safety schemes were simple based on the
current codes. It was up to the employer to consider this aspect and obtain
the best cost effective solution. Since the introduction of risk assessment
and the numerous solutions available to the fire safety profession it
is now incumbent on the person conducting a fire risk assessment to consider
costs. This can be achieved by comparing prices on the net and arriving
at an average price and you must also consider the cost of installation.
In this case a starting point and an idea of various types could be the
Fire
Door Retainers page at SafeLincs
Further Information
BS
7273-4:2007 - Code of practice for the operation of fire
protection measures. Actuation of release mechanisms for doors
BS
EN 1155:1997 Building hardware. Electrically powered hold-open
devices for swing doors. Requirements and test methods
This handout provides a general overview and basic information
on this topic. It may not apply to everyone, consequently to find out
if this guide applies to you and to get more information on this subject,
study all the relevant legislation, guides and British/European Standards.
Also you should seek advice from an expert on the subject or your local
Fire Safety Officer or Fire Safety Professional.
I would be much obliged if you would sign the guestbook
and make your comments about the web site. Also include your constructive
criticism on the site and inform me if any information which is out
of date so I can research it to bring it up todate. This will enable
me to improve the site and make it more relevant to its users.

Merseyside Fire Liaison Panel. Permission
is granted to print and photocopy this material for nonprofit educational
uses.
[Index]
This page was last checked and modified
on
Thursday, 8 July, 2010 22:26
|