|
Introduction
The purpose of this page is to allow you to understand
the basics of means of escape and not how to design a means of escape
from fire. There are many considerations, not covered here, in planning
means of escape, but it will give insight in how a means of escapes are
designed. It is based on the old prescriptive concepts but understanding
these principles will help in appling the modern risk based methods.
Definition of Means of Escape from Fire
Means of escape from fire is, at best, an inexact science
with only a few rules and formulae. However, the following definition
is widely acceptable: -
Means of Escape is a structural means, whereby a
safe route is provided for persons to escape in case of fire, from any
point in a building to a place of safety, clear of the building, without
outside assistance
Information required to design a means of escape
from Fire
You need to know the following information when designing
a means of escape from fire in a premises or building,
- Time of evacuation
- Travel distances
- Number of Occupants
- Calculation of Exit Widths
- Calculation of Minimum Number of Exits
Time of evacuation
Time of evacuation is dependent on on the following factors;
- Building construction
- Occupancy
The construction of buildings are divided into three basic
types,
- Class A - complete noncombustible construction,
i.e. elements of structure, floors, and walls. Supporting structure
of brick or concrete;
- Class B - traditional construction, i.e. noncombustible
walls with combustible floors;
- Class C - combustible construction, i.e. timber floors
and walls.
Based on these classes arbitrary evacuation times were
decided upon and the times that are generally accepted as -;
- Class 'A' construction - 3 minutes
- Class 'B' construction - 2.5 minutes
- Class 'C' construction - 2 minutes
These are not hard and fast times, and can be extended
or reduced according to the particular circumstances
Number of Occupants
You must consider the people normally in the building,
and the those who may use the building.
Number of Occupants
The number of occupants for an existing building with a
reasonably fixed population may be ascertained by questioning the responsible
person who owns or occupies the building. For buildings such as theatres
or cinemas, the number of seats provided should be counted.
Density Factor
In an unoccupied premises, to calculate the maximum numbers
of people permissible in any given occupancy you must refer to density
factors. The density factor may be defined as "the available floor
space per person".
Design codes for new buildings lay down specific density
factors, which will vary, dependent upon the intended use of the floor
space, i.e. lounge, restaurant, etc, check out the following documents,
- Building Regulations - Approved Document B Appendic
C1
- BS 9999 2008
To ascertain the maximum numbers of people, you need to
calculate the floor space, delete the area of permanent features, i.e.
stairs, toilets, lifts, escalators, corridors and other circulation spaces.
What is left is the usable floor space and this is divided by the density
factor giving you the number of person able to occupy that area.
Persons who may use the building
Occasional visitors to the building must be considered
and in the case of shops and departmental stores these people will out
number the people normally occupying the premises. In the case of retail
premises density factors will usually give the numbers other situations
a fair estimate must be made.
Calculating the Number of Occupants
Consider a retail premises consisting of a sales floor
canteen and offices. As different parts of the building are put to a different
uses therefore it is necessary to use different density factors. To calculate
the number of people, it is necessary to divide the floor area by the
floor space allowed per person.
Number of People = area of room or storey / floor space
per person
If floor space factors for the above example are:
-
Shop floor (main sales) - 2 m2 per person;
-
Offices - 5 m2 per person;
-
Canteen - 1 m2 per person;
and the relevant floor areas are:
-
Shop floor - 20 m x 30 m = 600 m2
-
Offices space - 8 m x 8 m = 64 m2
-
Canteen - 8 m x l0 m = 80 m2.
This is the total floor area - not the usable floor area.
It is therefore necessary now to deduct the floor area of the permanent
features in the area where they are situated
-
W.C. In shop = 10 m2
-
Stairs in shop = 15 m2 x 2 = 30 m2
-
W.C. In canteen = 10 m2.
-
Shop floor - 600 m2 - 40 m2 = 560 m2
-
Offices space - 64 m2 - 8 m = 64 m2
-
Canteen - 80 m2 x l0 m2 = 70 m2.
Therefore, the total number of people for which escape
routes must be designed is,
-
Shop = 560/2 = 280
-
Offices open plan = 64/5 = 13
-
Canteen = 70/1 = 70
TOTAL = 363 people
Therefore the number of exits should, be adequate for 363
people.
Travel Distance
Travel distance is measured from any point in the building
to a place of safety (i.e. relative or ultimate). Travel distance will
depend on how quickly people will react and make their escape and how
long it will be before the fire prevents that movement to the escape route.
Research done after the second world war came up with findings
that people in smoke, escaping to a place, clear of smoke traveled 40
feet per minute therefore with an escape times of 2 minutes a person could
travel 80 feet, 2.5 minutes 100 feet and 3 minutes 120 feet. It also showed
that if the exit allowed one person to Pass to 40 persons could escape
in a minute. These figures were accepted for sometime until codes of practice
appeared giving various travel distances for deferent occupancies however
they do reflect the post war studies.
If a room or compartment has two or more exits preferably
diametrical opposed, (Escape in more than one direction) then a person
escaping can turn their back on the fire. If there is only one exit then
a person may have to travel towards the fire (Escape in one direction
only) consequently the travel distance is reduced.
Places of Relative Safety
It is often necessary to devise a temporary place of safety,
such as when evacuating high buildings. This may be defined as a place
of comparative safety and includes any place, which puts an effective
barrier (normally 30 minutes fire resistance) between the person escaping
and the fire. Examples are as follows;
- A storey exit into a protected stairway or to
the lobby of a lobby approach stairway;
- A door in a compartment wall or separating wall
leading to an alternative exit;
- A door which leads directly to a protected stair
or a final exit via a protected corridor.
A staircase, which is enclosed throughout its height by
fire resisting structure and doors, can usually be considered to be a
place of comparative safety. In these cases, the staircase can be known
as "a protected route". However, the degree of protection to
staircases to enable them to be considered as a place of comparative safety
varies for differing building types, and is normally defined in the relevant
codes of practice.
BS 8300:2009. Design of buildings and their approaches to meet the needs
of disabled people, gives guidance on means of escape for disabled people.
Place of Ultimate Safety
Ideally this should be in the open air where dispersal,
away from the building, can be achieved. Escape routes should never discharge
finally into enclosed areas or yards unless the dispersal area is large
enough to permit all the occupants to proceed to a safe distance away.
Total dispersal in the open air therefore constitutes ultimate safety.
When inspecting any building, it is important to always follow the escape
route to its ultimate place of safety;
Calculation of Exit Widths
The width of exits required, depends on the number of occupants,
rate of flow and the 'flow time' and is expressed by the formula
U = N / (40 x T)
Where: -
U = number of units required;
N = number of occupants;
40 = standard rate of flow - constant;
T = Flow time (i.e. 3 mins for Class 'A', 2.5 mins for Class 'B' and
2 mins for Class 'C')
The resulting number of units may well result in less than
a whole number. If any fraction is greater than or equal to 0.3 it should
be rounded up.
It should be noted that it is not normal for doors to be
supplied in sizes compatible with the width of individual units, e.g.
a 750 mm door can only be regarded as 1 unit wide.
Calculation of Minimum Number of Exits
The minimum number of exits depends upon the number of
units of exit width required and the maximum size of any particular exit,
and is expressed by the formula
E = U / 4 + 1
E = number of exits
U = number of units of exit width (from exit width formula);
4 = size of largest exit permitted.
1 added to ensure there would always be at least one unit.
The result of this formula may well work out as a fraction,
and if this fraction is greater than or equal to 0.75, it should be rounded
up. Again, the + 1 in this formula is included to ensure that, in the
event of the U/4 element being less than 0.75, then at least one exit
would be provided to the room.
In most codes of practice, however, it is the norm for
2 exits to be required situations in which rooms are occupied by more
than 50 or 60 people, the reason being that the one exit required by the
above formula could well - in the worst possible scenario - become blocked
by the fire.
Therefore, in addition to the formula, an additional exit
equivalent to the largest size should be added; but where this is physically
impracticable, the numbers permitted must be reduced.
Example
A traditionally constructed room has been designed to accommodate
710 people. How many units of exit are required, and what is the minimum
number of exits.
a) U = N / (40 x T) = 720 / (40 x 2.5) = 710 / 100 =
7.1
This fraction is less than 0.3 therefore it is rounded up to 7 units
(b) E = U / 4 + 1 = 7 / 4 + 1 = 2.75
This fraction is equal to 0.75 therefore it is rounded up to 3 exits
Therefore, the answer is that a minimum of 3 exits should
be provided totaling 7 units, e.g. 2 x 2 units each + 1 x 3 units
However, we must consider the possibility of one of these exits being
obstructed by the fire, with the worst case being one of the largest being
lost. In our example, this would leave us with 2 exits of 2 units each
leaving just 4 units to discharge 710 people.
Therefore, keeping the exits as they are, these remaining
exits would need to be increased in size to accommodate our 710 people,
and in this case we would need to increase each exit to be 4 units wide
(i.e. 1950 mm each) in order to ensure the evacuation of our 710 people.
Therefore, by now providing 3 exits of 4 units width each,
we have allowed for one exit being blocked but still leave 8 units available
for the evacuation, which is now a greater capacity than is required.
A further adjustment could allow for one of the units to be a 3-unit exit
that would leave us with 7 units for evacuation - which is satisfactory.
We can transpose the formula for the number of units to
N = U x 40 x T in order to arrive at the maximum number of occupants allowed.
The distribution of alternative exits is important so as
to ensure that they can be effectively used in case one is blocked due
to a fire nearby. This is achieved by ensuring that the alternatives are
further apart than an angle of 45° from the farthest point in the
room from the exit.
DESIGNING A MEANS OF ESCAPE FROM FIRE
You now have the information needed to design a means of
escape from fire in a premises or building,
- Time of evacuation
- Travel distances
- Number of Occupants
- Calculation of Exit Widths
- Calculation of Minimum Number of Exits
Whilst these factors are present in all cases, it is not
so obvious that their importance will vary according to the circumstances.
Sometimes one, sometimes another, will assume greater importance in your
assessments and subsequent solution.
For example, a precast concrete manufacturer housed in
a single storey building constructed entirely of noncombustible materials.
Because of the construction, your considerations will probably centre
upon maximum travel distance to an exit within a reasonable period of
time.
Now consider a manufacturer using highly flammable materials,
you would be looking for a rapid evacuation in a very short time and the
fact that the building is completely noncombustible has little, effect.
In new building, and the occupancy is unknown the differences
required between the above two situations are considerable, and this can
cause great difficulty in planning means of escape. In such cases, the
means of escape must be designed to cater for the worst possible case.
Having considered the factors that will influence escape,
and having seen how these can be related to building type, it is important
to look at the stages in the process of escape and the maximum distances
people can be expected to travel.
Escape is generally considered in four distinct 'Stages'
as follows
Stage 1 - escape from the room or area of fire origin
Stage 2 - escape from the compartment of origin via the
circulation route to a protected stairway or an adjoining compartment
offering refuge
Stage 3 - escape from the floor of origin to the ground
level
Stage 4 - escape at ground level away from the building.
You need to study each floor plan and consider each room
or compartment, deciding if the travel distance from the furthest point
of that room or compartment to a place of comparative or ultimate safety
is less than the maximum travel distance.
You need to then calculate the number of occupants and
ascertain if the exits from the room or compartment to a place of comparative
or ultimate safety is adequate.
This handout provides a general overview and basic information
on this topic. It may not apply to everyone, consequently to find out
if this guide applies to you and to get more information on this subject,
study all the relevant legislation, guides and British/European Standards.
Also you should seek advice from an expert on the subject or your local
Fire Safety Officer or Fire Safety Professional.
I would be much obliged if you would sign the guestbook
and make your comments about the web site. Also include your constructive
criticism on the site and inform me if any information which is out
of date so I can research it to bring it up todate. This will enable
me to improve the site and make it more relevant to its users.

Merseyside Fire Liaison Panel. Permission
is granted to print and photocopy this material for nonprofit educational
uses.
[Index]
This page was last checked and modified
on
Thursday, 8 July, 2010 22:26
|